Amperage Rating
|
|
400 A
|
|
Cover Type
|
|
Medium Heat Cover (Red)
|
|
Nominal Current
|
|
400 A
|
|
Cross Sectional Area
|
|
93 mm²
|
|
Maximum System Voltage AC or DC (Per UL Listing)
|
|
600 V
|
|
Resistance R (for DC) at 20º C
|
|
0.000184 Ω/m
|
|
Impedance Z (for AC) at 20º C
|
|
0.000221 Ω/m
|
|
Maximum Allowable Ambient Temperature
|
|
25 ºC
|
|
Bar Length
|
|
4.5 m
|
|
Support Pitch Standard
|
|
1500 mm
|
|
Support Pitch Lateral
|
|
1125 mm
|
|
Minimum Pitch Centers Standard
|
|
43 mm
|
|
Expansion Sections
|
|
150 m
|
|
Minimum Bending Radius
|
|
1.5 m
|
|
Weight
|
|
10 lb 4.5 kg
|
|
Material
|
|