Roll formed of 1/32" material
The equivalent rectangle for all conductors is 1" x 1/4". Supports are required at intervals of: 3’ on curves, 3'-4" for lateral mount, 5' standard.

All roll-formed conductors are supplied assembled with connector pins and cover. Joint covers and joint keepers are furnished with each order as required.
Unit of Measure
Items
Bar 40_350

Stainless Clad Copper Bar 250A - with Connector Pins

Bar 40_350

Stainless Clad Copper Bar 250A - with Connector Pins

Bar 40_350

Stainless Clad Copper Bar 250A - with Connector Pins

Bar 40_350

Stainless Clad Copper Bar 250A - with Connector Pins

Bar 40_350

Stainless Clad Copper Bar 250A - with Connector Pins
Ampacity (continuous duty) N/A 250 A
Material N/A Stainless Clad Copper Laminate
Cover Type N/A Rigid PVC N/A Rigid PVC N/A Medium Heat N/A Medium Heat N/A High Heat
Weight N/A 6.6 lb0.65 lb/ft N/A 3.3 lb0.65 lb/ft N/A 6.2 lb0.65 lb/ft N/A 3.1 lb0.65 lb/ft N/A 7.1 lb0.65 lb/ft
Length N/A 10 ft N/A 5 ft N/A 10 ft N/A 5 ft N/A 10 ft
Cross Sectional Area N/A 0.1477 in²
Expansion Coefficient N/A 0.000009 ºF
Resistance R (for DC) at 20º C
N/A 100 µΩ/ft
Reactance X (60 Hz)
N/A 60 µΩ/ft
Impedance Z (60Hz)
N/A 116 µΩ/ft
Support Spacing N/A 5 ft
Normal Ambient N/A -10 to 160 ºF N/A -10 to 160 ºF N/A -25 to 250 ºF N/A -25 to 250 ºF N/A -60 to 400 ºF