Print Back
Roll formed of 1/32" material
The equivalent rectangle for all conductors is 1" x 1/4". Supports are required at intervals of: 3' on curves, 3'-4" for lateral mount, 5' standard.

The solid copper conductors are supplied in 20' lengths, covered, with connector clamp and case. Conductor bar and covers may be ordered separately for replacement purposes.
Bar 500
Bar 40_500dim
Unit of Measure
Items Bar 500
11016
Solid Copper Bar 500A - uses Clamped Joints
Bar 500
11017
Solid Copper Bar 500A - uses Clamped Joints
Bar 500
11035
Solid Copper Bar 500A - uses Clamped Joints
Bar 500
11036
Solid Copper Bar 500A - uses Clamped Joints
Bar 500
11054
Solid Copper Bar 500A - uses Clamped Joints
Ampacity (continuous duty) N/A 500 A
Material N/A Solid Copper
Cover Type N/A Rigid PVC N/A Rigid PVC N/A Medium Heat N/A Medium Heat N/A High Heat
Weight N/A 23.6 lb0.16 lb/ft N/A 11.8 lb0.16 lb/ft N/A 22.1 lb0.16 lb/ft N/A 11.0 lb0.16 lb/ft N/A 24.6 lb0.16 lb/ft
Length N/A 20 ft N/A 5 ft N/A 20 ft N/A 5 ft N/A 20 ft
Cross Sectional Area N/A 0.1477 in²
Expansion Coefficient N/A 0.000009 ºF
Resistance R (for DC) at 20º C N/A 40 µΩ/ft
Reactance X (60 Hz) N/A 60 µΩ/ft
Impedance Z (60Hz) N/A 70 µΩ/ft
Support Spacing N/A 5 ft
Normal Ambient N/A -10 to 160 ºF N/A -10 to 160 ºF N/A -25 to 250 ºF N/A -25 to 250 ºF N/A -60 to 400 ºF