Standard Conductor Bar Cut Lengths for Hevi-Bar II Conductor Bar
Conductor Bars
Unit of Measure
Items |
/Asset/Heviconductor-Bar500A.jpg 27583 Standard Conductor Bar Cut Lengths for Hevi-Bar II Conductor Bar |
/Asset/Heviconductor-Bar500A.jpg 50260 Standard Conductor Bar Cut Lengths for Hevi-Bar II Conductor Bar |
/Asset/Heviconductor-Bar500A.jpg 38926 Standard Conductor Bar Cut Lengths for Hevi-Bar II Conductor Bar |
/Asset/Heviconductor-Bar500A.jpg 39225 Standard Conductor Bar Cut Lengths for Hevi-Bar II Conductor Bar |
/Asset/Heviconductor-Bar700A.jpg 24529 Standard Conductor Bar Cut Lengths for Hevi-Bar II Conductor Bar |
|||||
Amperage Rating | N/A 500 A | N/A 500 A | N/A 500 A | N/A 500 A | N/A 700 A | |||||
Material | N/A PVC | N/A PVC | N/A PVC | N/A Polycarbonate | N/A PVC | |||||
Maximum Temperature | N/A 160 ºF | N/A 160 ºF | N/A 160 ºF | N/A 250 ºF | N/A 160 ºF | |||||
Cover Type | N/A Phase / Indoors (Orange) | N/A Ground / Indoors (Green) | N/A Phase & Ground / Outdoors UV Stable (Black) | N/A Phase & Ground/ Indoors & Outdoors (Red) | N/A Phase / Indoors (Orange) | |||||
Weight | N/A 0.81 lb/ft | N/A 0.81 lb/ft | N/A 0.81 lb/ft | N/A 0.81 lb/ft | N/A 1.31 lb/ft | |||||
Length | N/A 5 to 29 ft | |||||||||
Cross Sectional Area | N/A 0.45 in² | N/A 0.45 in² | N/A 0.45 in² | N/A 0.45 in² | N/A 0.70 in² | |||||
Maximum System Voltage AC or DC (Per UL Listing) |
N/A 600 V | N/A 600 V | N/A 600 V | N/A 600 V | N/A 4160 V600 V | |||||
Resistance R (for DC) at 20º C | N/A 3.27 x 10-5 c/ft | N/A 3.27 x 10-5 c/ft | N/A 3.27 x 10-5 c/ft | N/A 3.27 x 10-5 c/ft | N/A 2.11 x 10-5 c/ft | |||||
Phase Corrected Impedance Z at 20º C | N/A 5.40 x 10-5 c/ft | N/A 5.40 x 10-5 c/ft | N/A 5.40 x 10-5 c/ft | N/A 5.40 x 10-5 c/ft | N/A 4.21 x 10-5 c/ft | |||||
Support Spacing | N/A 5 ft | N/A 5 ft | N/A 5 ft | N/A 5 ft | N/A 7.5 ft | |||||
Spacing between Conductors | N/A 3.0 in | |||||||||
Minimum Bending Radius | N/A 8 ft | N/A 8 ft | N/A 8 ft | N/A 8 ft | N/A 10 ft | |||||
Normal Ambient | N/A -40 to 104 ºF | N/A -40 to 104 ºF | N/A -40 to 104 ºF | N/A -40 to 200 ºF | N/A -40 to 104 ºF | |||||
Dielectric Strength | N/A 450 V/mil | N/A 450 V/mil | N/A 450 V/mil | N/A 600 V/mil | N/A 450 V/mil | |||||
Volume Resistivity | N/A >1012 Ω/mil | N/A >1012 Ω/mil | N/A >1012 Ω/mil | N/A >1013 Ω/mil | N/A >1012 Ω/mil | |||||
Flame Test | N/A Self Extinguishing | |||||||||
Specific Density | N/A 1.5 g/cm³ | N/A 1.5 g/cm³ | N/A 1.5 g/cm³ | N/A 1.15 g/cm³ | N/A 1.5 g/cm³ | |||||
Available Accessories | N/A Pick-up Guides for discontinuous systems Thermostatically controlled heater wire system, for ice and snow environments Transfer Caps for switches Vertical and horizontal curves | N/A Pick-up Guides for discontinuous systems Thermostatically controlled heater wire system, for ice and snow environments Transfer Caps for switches Vertical and horizontal curves | N/A Pick-up Guides for discontinuous systems Thermostatically controlled heater wire system, for ice and snow environments Transfer Caps for switches Vertical and horizontal curves | N/A Pick-up Guides for discontinuous systems Thermostatically controlled heater wire system, for ice and snow environments Transfer Caps for switches Vertical and horizontal curves | N/A Pick-up Guides for discontinuous systems Transfer Caps for switches Vertical and horizontal curves | |||||
Corrosion Protection Option | N/A Stainless Steel Zinc Plated | |||||||||
|